Three-Phase Integrated Lightning arrester
Product Details:
| Place of Origin | China (Mainland) |
|---|
Payment & Shipping Terms:
| Payment Terms: | L/C,T/T |
|---|
Detailed Product Description
Three-Phase Integrated Lightning arrester
| Table1 FBP-A series Motor Type | ||||
| Motor Rated voltage(KV) | (r.m.s) | 6.3 | 10.5 | |
| lightning Rated voltage(KV) | 7.6 | 12.7 | ||
| Power frequency discharge voltage(KV) | 15.0 | 25.0 | ||
| Reference voltage at 1mA Dc(KV) | (Crest) | 11.2 | 18.6 | |
| 1.2/50μS Impulse discharge voltage(KV) | 17.0 | 29.0 | ||
| 100A Swit ching current impulse(KV) | 13.6 | 23.0 | ||
| 25KA Lightning current ipmulse(KV) | 17.0 | 29.0 | ||
| 2000μS Spupre wave Impulse curent(A) | 400 | 400 | ||
| Safe net distaence()(mm) | 95 | 120 | ||
| furface Leakage distance()(mm) | 140 | 235 | ||
| Smallest separate distance(mm) | 115 | 145 | ||
| Table2 FBP-B series Vacuum Civcuit Breakev | ||||
| System Voltage(KV) | (r.m.s) | 6 | 10 | 35 |
| lightning Rated voltage | 7.6 | 12.7 | 42 | |
| Power frequency discharge voltage(KV) | 16.0 | 26.0 | 80.0 | |
| Reference voltage at 1mA Dc(KV) | (Crest) | 14.4 | 24 | 73 |
| 1.2/50μS Impulse discharge voltage(KV) | 24.0 | 41.0 | 124.0 | |
| 500A Switching current impulse(KV) | 19.0 | 32.0 | 99.0 | |
| 2000μS Spupre wave Impulse curent(A) | 400 | 400 | 400 | |
| Safe net distaence()(mm) | 95 | 120 | 285 | |
| furface Leakage distance()(mm) | 140 | 235 | 1020 | |
| Smallest separate distance(mm) | 115 | 145 | 470 | |
| Table3 FBP-C series Capacitor Type | ||||
| System Voltage | (r.m.s) | 6 | 10 | 35 |
| lightning Rated voltage(KV) | 7.6 | 12.7 | 42 | |
| Power frequency discharge voltage(KV) | 16.0 | 26.0 | 80.0 | |
| Reference voltage at 1mA Dc(KV) | (Crest) | 14.4 | 24 | 73 |
| 1.2/50μS Impulse discharge voltage(KV) | 24.0 | 41.0 | 124.0 | |
| 500A Switching current impulse(KV) | 19.0 | 32.0 | 99.0 | |
| 2000μS Spupre wave Impulse curent(A) | 400 | 400 | 400 | |
| Safe net distaence()(mm) | 95 | 120 | 285 | |
| furface Leakage distance()(mm) | 140 | 235 | 1020 | |
| Smallest separate distance(mm) | 115 | 145 | 470 | |
| Table4 FBP-O series() | |||
| lightning Rated voltage | MotorRated voltage | lightningCurrent impulse Residual Voltage8/20us ≤ | Reference Voltage at ImA Dc1mA IMA DC ≥ |
| KV(rms) | KV(rms) | KV(crest) | KV(crest) |
| 4.8 | 6.3 | 12.0 | 6.8 |
| 8 | 10.5 | 19.0 | 11.4 |
Three-Phase Integrated Lightning arrester
Send your message to this supplier
Didn't find what you're looking for? Post a buying lead.
Products
- Fused Cut Out/ Disconnectors [4]
- cable accessories [17]
- protection fitting [7]
- splicing fitting [4]
- composite insulator [9]
- Insulated fitting [19]
- lightning arrester [44]
- cable fitting and clamp [25]
- hardware [6]
- suspension clamp [4]
- strain clamp [3]
- Link Fitting [23]
Company Info
Qingdao Ferry Electric And Metal Co., Ltd.
[China (Mainland)]
[Verified Member]
City: Qingdao
Province/State: Shandong
Country/Region : China (Mainland)
Business Type:Manufacturer, Trading Company
Online Postings: Products